SEC.
In all areas of special flood hazards the following provisions are required:
All new construction and substantial improvements shall be designed (or modified) and
adequately anchored to prevent flotation, collapse or lateral movement of the structure resulting
from hydrodynamic and hydrostatic loads, including the effects of buoyancy;
All new construction or substantial improvements shall be constructed by methods and practices
that minimize flood damage;
All new construction or substantial improvements shall be constructed with electrical, heating,
ventilation, plumbing, and air conditioning equipment and other service facilities that are designed
and/or located so as to prevent water from entering or accumulating within the components during
conditions of flooding.
All new construction or substantial improvements shall be constructed with electrical, heating,
ventilation, plumbing, and air conditioning equipment and other service facilities that are designed
and/or located so as to prevent water from entering or accumulating within the components during
conditions of flooding.
All new and replacement water supply systems shall be designed to minimize or eliminate
infiltration of flood waters into the system;
New and replacement sanitary sewage systems shall be designed to minimize or eliminate
infiltration of flood waters into the system and discharge from the systems into flood waters; and,
On-site waste disposal systems shall be located to avoid impairment to them or contamination
from them during flooding. (Ord. No. 610, adopted 12/19/74; Ord. No. 611, adopted 01/16/75;
Ord. No. 791, adopted 02/16/78; Ord. 87-770, adopted 02/19/87; Ord. No. 89-1053, adopted
03/16/89)
SEC.
a. Require that all manufactured homes to be placed within Zone A shall be installed using
methods and practices which minimize flood damage. For the purpose of this requirement,
manufactured homes must be elevated and anchored to resist flotation, collapse or lateral
movement. Methods of anchoring may include, but are not limited to, use of over-the-top or
frame ties to ground anchors. This requirement is in addition to applicable State and local an
choring requirements for resisting wind forces.
b. All manufactured homes shall be in compliance with Division 5, Section 7-042.00(1).
c. Require that all manufactured homes to be placed or substantially improved within Zones A1-
30, AH and AE on the community's FIRM be elevated on a permanent foundation such that the
lowest floor of the manufactured home is at or above the base flood elevation; and be securely
anchored to an adequately anchored foundation system in accordance with the provision of
Section 7-042.00(4) of this Division. (Ord. No. 610, adopted 12/19/74; Ord. No. 611, adopted
01/16/75; Ord. No. 791, adopted 02/16/78; Ord. No. 87-770, adopted 02/19/87; Ord. No. 89-
1053, adopted 03/16/89)
(5) Construction Sites - Storm Water Runoff
a. A permit shall be required for the clearing, grubbing, grading, displacement or removal of dirt
(hereafter referred to as dirt work) for any properties not specifically exempted as per Paragraph
(c) of this Section. This permit shall be in the form of an approval of the Culvert Data Sheet, the
Permit Data Review Sheet, a general work order or land clearing permit presently required for
construction activity to occur. The ordinance shall be administered by Department of Engineering or
any other parish personnel that should be necessary.
b. A detailed description of dirt work, boundaries of the areas to be disturbed and the proposed
sediment retention measures must accompany the building permit or development proposal and be
reviewed by the Department of Engineering before approval of the Culvert Data Sheet or the Permit
Data Tracking Sheet or the issuance of a general work order.
c. Exemptions
A.
Agricultural land management practices and construction of agricultural structures as
defined in the St. Tammany Parish Land Use Ordinance No. 523;
2. Mining, quarrying, processing of rock, sand, gravel, aggregate or clay where established
and provided for by law;
3. Activities undertaken on forest land in the production and harvesting of timber when
approved via an agricultural clearing, timber harvesting or rural clearing permit in
accordance with St. Tammany Parish Land Use Ordinance No. 523;
4. Single family residences, and related accessory structures or uses, when the disturbed
area comprises of less than 50% of the lot or parcel and is located at least 10 feet from
all property lines.
d.
Requirements
1.
The owner, builder or developer of a construction project shall cause the placement of a
required sediment control measure for all side slope and down slope boundaries of a
construction area, unless a sedimentation basin designed to accommodate 3600 cubic feet
of water and sediment for each acre of disturbed property is provided .
2. The owner, builder or developer will further cause the placement of said sediment control
measure around all drainage structure inlets which flow into a public drainage system, or a
drainage system which is intended to be dedicated to the public.
e. Sediment Retention Measures
g. Provision of sediment retention measures on site does not release the builder/developer from
responsibilities as outlined in Section 40-071.01of Appendix B (Subdivision Regulations) of the St.
Tammany Parish Code of Ordinances should the retention measures fail to prevent sediment runoff.
The Director of the Department of Engineering may release the builder/developer from the provisions
of this Section if it is determined that the failure of sediment control measures is not attributable to
faulty installation or maintenance of the required retention measures.
h.
Enforcement
Violations will be processed by the appropriate Code Enforcement, Department of Engineering or
Permit Inspections personnel using standard code violation protocol.
(Subsection 5 per Ord. 99-3156, adopted 10/21/99)
SEC.
A registered professional engineer or architect shall submit a certificate of elevation, documented on
the Federal Emergency Management Agency Form 81-31 or subsequent agency form, to the
Floodplain Administrator that the standards of this Section and as per Article 4, Section c.(1)a. (St.
Tammany Parish Code of Ordinances Chapter 7, Division 4, Section 7-023.02(1)a.), has been satis
factorily met. (amended by Ord. No. 92-1597, adopted 05/21/92)
SEC.
Located within the areas of special flood hazard established in Division 3, Section 7-022.00, are
areas designated as Coastal High Hazard Areas (Zones V1-30, VE and/or V). These areas have
special flood hazards associated with high velocity waters from tidal surges and hurricane wave
wash; therefore, in addition to meeting all provisions outlined in this Ordinance, the following
provisions must also apply:
(1) Obtain the elevation (in relation to mean sea level) of the bottom of the lowest structural
member of the lowest floor (excluding pilings and columns) of all new substantially
improved structures, and whether or not such structures contain a basement. The
Floodplain Administrator shall maintain a record of all such information.
(2) All new construction shall be located landward of the reach of mean high tide.
(3) All new construction and substantial improvements shall be elevated on pilings and
columns so that:
(i) the bottom of the lowest horizontal structural member of the lowest floor (excluding
the pilings or columns) is elevated to or above the base flood level;
(ii) the pile or column foundation and structure attached thereto is anchored to resist
flotation, collapse and lateral movement due to the effects of wind and water loads
acting simultaneously on all building components. Wind and water loading values
shall each have a one (1%) percent chance of being equaled or exceeded in any
given year (100-year mean recurrence interval);
(iii) a registered professional engineer or architect shall develop or review the structural
design, specification and plans for the construction and shall certify that the design
and methods of construction to be used are in accordance with accepted standards
of practice for meeting the provisions of this paragraph (3)(i), (ii) and (iii) of this
Section.
(4) Provide that all new construction and substantial improvements have the space below
the lowest floor either free of obstruction or constructed with non-supporting breakaway
walls, open wood lattice work, or insect screening intended to collapse under wind and
water loads without causing collapse, displacement or other structural damage to the
elevated portion of the building or supporting foundation system.
For the purpose of this Section, a breakaway wall shall have a design safe loading resistance of
not less than ten (10 lbs.) and nor more than twenty (20 lbs.) pounds per square foot. Use of
breakaway walls which exceed a design safe loading resistance of twenty (20 lbs.) pounds per
square foot (either by design or when so required by local or State codes) may be permitted only if a
registered professional engineer or architect certifies that the designs proposed meet the following
conditions:
(i) breakaway wall collapse shall result from a water load less than that which would
occur during the base flood; and
(ii) the elevated portion of the building and supporting foundation system shall not be
subject to collapse, displacement or other structural damage due to the effects of
wind and water loads acting simultaneously on all building components (structural
and nonstructural). Maximum wind and water loading values to be used in this
determination shall each have one (1%) percent chance of being equaled or exceeded
in any given year (100-year mean recurrence interval).
(5) If breakaway walls are utilized, such enclosed space shall be usable solely for parking of
vehicles, building access or storage. Such space shall not be used for human habitation.
(6) Prohibit the use of fill for structural support of buildings.
(7) Prohibit man-made alteration of sand dunes and mangrove stands which would increase
potential flood damage.
(8) Any alteration, repair, reconstruction or improvements to a structure started after the
enactment of this Ordinance shall not enclose the space below the lowest floor unless
breakaway walls are used as provided for in Division 5.
(9) Prior to construction, plans for any structure that will have breakaway walls must be
submitted to the Floodplain Administrator for approval. (Ord. 87-770, adopted
02/19/87; Ord. No. 89-1053, adopted 03/16/89)
SEC. 7-046.00 - 7-048.99 Reserved
SEC.
Violation of the provisions of this Ordinance or failure to comply with any of its requirements
shall constitute a misdemeanor and upon conviction thereof, the violator(s) shall be fined not less
than One Hundred ($100.00) Dollars not more than Three Hundred ($300.00) Dollars or imprisoned
for not more than thirty (30) days, or both, and in addition thereto shall pay all costs and expenses
involved in the case; however, the maximum of aggregated fines are not to exceed One Thousand
($1,000.00) Dollars. Each day such violation continues shall be considered as a separate offense all
in accordance with Section 1-008.00 of the Code of Ordinances of St. Tammany Parish, Louisiana.
The owner or tenant of any building, structure, premises, or part thereof, any architect, builder,
contractor, agent or other person who commits, participates in, assists in or maintains such violation
may each be found guilty of a separate offense and suffer the penalties herein provided.
Nothing herein contained shall prevent the Parish from taking such other lawful actions as is
necessary to prevent or remedy any violation. (Ord. No. 89-1053, adopted 03/16/89)
SECS. 7-049.02 - 7-049.99 Reserved
SEC.
(1)
All commercial, industrial and institutional uses that require a building permit shall submit a
drainage and paving plan with the permit application. Requirements are set forth in below in
Sec. 7-051.00. Said plan shall be forwarded to the Parish Engineer for review and approval
before the issuance of a building permit.
assessed to the developer. The Parish Engineer shall have final authority on approval of the
permit application.
SEC.
In order to expedite the drainage plan review for all commercial, industrial and institutional
developments, the Department of Engineering requests the following documents be provided:
(1)
A vicinity map indicating the location of the proposed project
7-050.00 Drainage and Paving Plan (Commercial, Industrial and Institutional Developments)
The purpose and intent of this section is to require a drainage and paving plan to be stamped
and certified by a Licensed Louisiana State Registered Engineer for construction of commercial,
industrial and institutional developments, with the goal of improving pre-development runoff and
reducing post-development runoff based on a ten (10) year storm event.
(2)
It shall be the responsibility of the developer and design engineer to create a site
development plan that will complement the drainage and paving plan utilizing site design
criteria so as to result in the reduction of runoff from post-development.
(3)
The drainage and paving plan shall be stamped and certified by a Licensed Louisiana State
Registered Engineer and shall meet the following criteria:
(i)
Parcels 0-2 acres in size shall be required to reduce pre-development peak
runoff by at least 10%, with on-site detention ponds optional.
(ii)
Parcels 2-5 acres in size shall be required to reduce pre-development peak
water runoff by at least 15%, with on-site detention ponds required.
(iii)
Parcels 5 acres and larger shall be required to reduce pre-development
peak runoff by at least 25%, with on-site detention ponds required.
(4)
A combination of detention methods may be utilized to meet the criteria as established
above. Off-site detention facilities may be utilized if approved by the Parish Engineer.
(5)
Developments located within the boundaries of Gravity Drainage District No. 5 shall also
submit their drainage and paving plans to the District at the time permit application is made
to the Parish. A building permit shall not be issued until the Drainage District has had an
opportunity to review and make comment on the proposed plans to the Parish Engineer. All
costs associated with the review of the plans by the Parish and Drainage District shall be
(Amended by Ord. 04-0933, adopted 07/01/2004)
7-051.00 Documents Required For Drainage and Paving Plan Review
(2)
A pre-development drainage plan (existing conditions)
(3)
Identify fill area(s) and associated fill depth(s)
(4)
A post development drainage plan
(5)
If building has down spouts, an architect's drawing is required
(6)
If the outfall needs to discharge to the ditch or pond, the invert elevations of associated
culvert(s) and bottom elevation of accepted ditch or pond shall be provided
(7)
If driveway culvert needs to be installed at the state highway ditch, an approval sheet from
the state shall be provided prior to the Parish approval
(8)
A hydrological analysis of both pre-development and post-development runoff shall be
provided. The hydrological analysis shall meet applicable Parish Ordinances
(9)
If the site is located in an area where known drainage problems exist, a drainage basin study
can be required to demonstrate compatibility with surrounding properties
(10)
The Department of Engineering reserves the right to hold the Certificate of Occupancy in
order to allow for a final inspection.
(All the above drawings and hydrological analysis need to be stamped and certified {signature and
date} by a Professional Engineer Registered in the State of Louisiana.)
(Ord. 98-2899, adopted 06/18/98)